Description Notes
Update mode on all
The running mode for all controllers in the power management system is updated
to the selected mode.
Store common settings See Handling settings for sections in Option G5 Power management.
Open MB Open the mains breaker.
Close MB Close the mains breaker.
Auto start/stop ON = Start, OFF = Stop.
Autoswitch off Auto-switch is not enabled.
Autoswitch static Auto-switch enabled for static section.
Autoswitch dynamic Auto-switch enabled for dynamic section.
Autoswitch all Auto-switch enabled for all sections.
Activate MB parallel Mains breaker in parallel is activated (parameter 8182).
Deactivate MB parallel Mains breaker in parallel is deactivated (parameter 8182).
Activate no break transfer No break transfer is activated.
Deactivate no break transfer No break transfer is deactivated.
Activate MB close failure start MB close failure start is activated.
Deactivate MB close failure start MB close failure start is deactivated.
Select three phase system Sets the controller to work in a three-phase system.
Select split L1L3 phase system Sets the controller to work in a two-phase system (L1-L3).
Select split L1L2 phase system Sets the controller to work in a two-phase system (L1-L3).
Select single phase system Sets the controller to work in a single-phase system (L1).
Inductive reference Inductive cos phi reference.
Capacitive reference Capacitive cos phi reference.
Act. power offset [1-3] Activate the selected power reference offset.
Deact. power offset [1-3] Deactivate the selected power reference offset.
Act. cos phi offset [1-3] Activate the cos phi reference offset.
Deact. cos phi offset [1-3] Deactivate the cos phi reference offset.
MB close inhibit Prevents the mains breaker from closing.
Reset horn Reset the horn relay.
Reset I max. demand Reset the peak current detected in the controller.
Reset I thermal demand Reset the thermal current detected in the controller.
Pulse counter [1-2] Increase the selected pulse counter.
Reset pulse counter [1-2] Reset the selected pulse counter.
Set parameter [1-2] Select the parameter set for busbar nominal settings.
Set BB U
NOM
= Mains U
NOM
Busbar nominal voltage is considered equal to the mains nominal voltage.
Mains sync. inhibit activate Activates the close inhibit functionality on the mains breaker.
Mains sync. inhibit deactivate Deactivates the close inhibit functionality on the mains breaker.
Ack. mains protection alarms
Acknowledges all mains alarms including: 1270-1430, 1660, 1700, 1960, 1970,
7480-7490.
Mains Okay
This function can be used if an input has been configured to Mains Okay. When it
is set, the command Mains Okay is given. This command is sometimes called
External Mains Okay.
Application note 4189341276B EN Page 42 of 50

Table of Contents

Other manuals for Deif AGC-4 Mk II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deif AGC-4 Mk II and is the answer not in the manual?

Deif AGC-4 Mk II Specifications

General IconGeneral
BrandDeif
ModelAGC-4 Mk II
CategoryController
LanguageEnglish

Related product manuals