Description Notes
TB Direct close - fast
TB Direct close on dead BA and dead
BB
TB Direct close - skip power capacity
Activate CBE
Activates close before excitation for the tie breaker. This command is usually used with
asynchronous gensets.
Deactivate CBE Deactivate close before excitation for the tie breaker.
GG Test CBE relay(s)
5.11 CAN commands
More information
See Option G5 Power management for information.
5.12 Display
Description Notes
Set display [1-3] to primary When more displays are used, set display [1-3] as the primary.
Act. view [1-20] on display [1-3] Activate a specific view on display [1-3].
Act. power reference menu on display
[1-3]
Makes the menu 7050 "Fixed Power set" appear on display [1-3].
Act. test power reference menu on
display [1-3]
Makes the menu 7040 "Test" appear on display [1-3].
Act. cos phi reference menu on
display [1-3]
Makes the menu 7050 "Fixed Power set" appear on display [1-3].
5.13 Static synchronisation type
These commands are only available for genset controllers.
Description
Notes
GB: breaker Set GB to Breaker Sync in static sync.
GB: infinite Set GB to Infinite Sync in static sync.
MB: breaker Set MB to Breaker Sync in static sync.
MB: infinite Set MB to Infinite Sync in static sync.
5.14 GOV/AVR control
These commands are only available for genset controllers.
Description
Notes
GOV increase Speed governor control output.
GOV decrease Speed governor control output.
Freeze Gov. regulation Speed governor control output.
AVR increase AVR voltage control output.
Application note 4189341276B EN Page 48 of 50