2. General description
2.1 Introduction
2.1.1 Introduction to M-Logic
The M-Logic is a small logic controller incorporated in the AGC controller. Even though it is a logic controller, it must not be confused
with a PLC. The M-Logic can be compared with a PLC limited in functionality and can only be used for uncomplicated tasks.
The M-Logic can carry out binary control functions only; there are no possibilities for analogue reading and/or control functions.
The M-Logic can be programmed from the free PC tool, DEIF Utility Software (USW version 3). The USW can be downloaded from
DEIFs web page: www.deif.com/software
M-Logic setting is done in command lines. There are 40 lines, and each line contains three events, two operators and one output
with a possibility to make a time delay.
If two operators are not enough, a number of virtual events can be used to pass the control on to another line and carry on there.
This makes it possible to build larger event-based controls.
Application note 4189341276B EN Page 7 of 50