3.6 Status texts
Status text Description
ACCESS LOCK The configurable input is activated, and the operator presses one of the blocked keys.
ADAPT IN PROGRESS The AGC is receiving the application that it has just connected to.
AMF ACTIVE The controller is in auto mode during a mains failure.
AMF AUTO The mains controller is in auto mode and ready to respond.
AMF MAN The controller is in manual mode and waiting for operator input.
AMF SEMI The controller is in semi-automatic mode and waiting for operator input.
Applying IP config.
The IP settings have been changed, so the controller is updating the configuration (this takes
about 30 seconds).
AUTO OPERATION
Power management, BTB controller: Controller in Auto, but not ready for breaker operation (due
to an active BTB trip alarm).
Aux. test ##.#V ####s The battery test is activated.
BB A BLOCKING Due to a problem on busbar A, the BTB controller cannot close the BTB.
BB B BLOCKING Due to a problem on busbar B, the BTB controller cannot close the BTB.
BB BLOCKED BY GB## Power management: GB## has a position failure.
BB BLOCKED BY MB## Power management: MB## has a position failure.
BB BLOCKED BY TB## Power management: TB## has a position failure.
BLACKOUT ENABLE Genset controller: There is a CAN failure in a power management application.
BLOCKED FOR CLOSING Power management, BTB controller: Last open BTB in a ring busbar.
BROADCAST ABORTED Power management: Broadcast terminated.
BROADCAST COMPLETED Power management: Successful broadcast of an application.
BROADCASTING APPL. #
Power management: Broadcast one of the four applications from one controller to the other AGCs
in the power management system, through the CAN line.
BTB XX DIVIDING SEC. Power management, Genset controller: BTB XX is dividing two sections in an island application.
BTB TRIP EXTERNALLY Some external equipment has tripped the breaker. An external trip is logged in the event log.
BTB## BLOCKED Power management: # is replaced by A or B depending on where the problem is located.
BLOCK Block mode is activated.
BTB RACKED OUT
The Breaker racked out digital input is actived. Position failure and external trip alarms from the
racked out breaker will not interfere with the rest of the system.
XXXX Busbar blocked Power management: Power sources cannot connect because breaker feedback is missing.
CBE config relay/DVC
CBE is enabled in parameter 2254, but no AVR relay or DVC 310/D510C/DVC 550 is configured.
The CBE sequence will not be executed.
CHANGING PRIORITY A manual priority change is being applied.
COMPENSATION FREQ. Compensation is active. The frequency is not at the nominal setting
COOLING DOWN Cooling down period is activated and indefinite (the cooling down timer is set to 0.0 s).
COOLING DOWN ###s Cooling down period is activated.
DELOAD The controller is decreasing the load of the genset in order to open the breaker.
DELOADING BTB XX Genset controllers are load sharing asymmetrically to de-load BTB XX.
DELOADING MB XX Genset controllers are increasing their load to de-load MB XX.
DELOADING TB XX Genset controllers are decreasing their load to de-load TB XX.
OPERATOR'S MANUAL 4189340690E EN Page 18 of 24