Status text Description
DERATED TO #####kW Displays the ramp down set point.
DG BLOCKED FOR START The generator has stopped and has active alarm(s).
DIVIDING SEC IN ###s The BTB will open in ###s.
DIVIDING SECTION Power management: A BTB controller is dividing two sections in an island application.
DRY ALTERNATOR AUTO The mains controller is in auto mode and ready to respond.
DRY ALTERNATOR MAN The controller is in manual mode and waiting for operator input.
DRY ALTERNATOR SEMI The controller is in semi-automatic mode and waiting for operator input.
DRYING ALTERNATOR The controller is in auto mode and drying the alternator.
EXTERNAL START ORDER A planned AMF sequence is activated (without a mains failure).
EXT. STOP TIME ###s
FIXED POWER ACTIVE The controller is in auto mode and supplying fixed power.
FIXED POWER AUTO The mains controller is in auto mode and ready to respond.
FIXED POWER MAN The controller is in manual mode and waiting for operator input.
FIXED POWER SEMI The controller is in semi-automatic mode and waiting for operator input.
FULL TEST Test mode is activated.
FULL TEST ###.#min Test mode activated and test timer counting down.
GB AND MB RACKED OUT
The Breaker racked out digital input is activated. Position failure and external trip alarms from the
racked out breakers will not interfere with the rest of the system.
GB ON BLOCKED The generator is running, the GB is open and there is an active Trip GB alarm.
GB RACKED OUT
The Breaker racked out digital input is activated. Position failure and external trip alarms from the
racked out breaker will not interfere with the rest of the system.
GB TRIP EXTERNALLY
Some external equipment (not the controller) has tripped the breaker. An external trip is logged in
the event log.
GENSET STOPPING Cooling down has finished.
Hz/V OK IN ###s
The voltage and frequency on the genset is OK. When the timer runs out the generator breaker
can be closed.
IDLE RUN The Idle run function is active. The genset will not stop until the timer has expired.
IDLE RUN ###.#min The timer in the Idle run function is active.
ISLAND ACTIVE The controller is in auto mode and supplying power while not connected to a mains supply.
ISLAND AUTO The mains controller is in auto mode and ready to respond.
ISLAND MAN The controller is in manual mode and waiting for operator input.
ISLAND SEMI The controller is in semi-automatic mode and waiting for operator input.
LOAD TAKEOVER AUTO The mains controller is in auto mode and ready to respond.
LOAD TAKEOVER MAN The controller is in manual mode and waiting for operator input.
LOAD TAKEOVER SEMI The controller is in semi-automatic mode and waiting for operator input.
LOAD TEST Test mode is activated.
LOAD TEST ###.#min Test mode activated and test timer counting down.
LTO ACTIVE The controller is in auto mode and taking over the load.
MAINS FAILURE Mains failure and mains failure timer expired.