The following adjustments must be made to make the system ready for the three-phase measuring (example
400/230V AC):
Setting Adjustment Description Adjust to
value
6004 G nom. voltage Phase-phase voltage of the generator 400V AC
6041 G transformer Primary voltage of the G voltage transformer (if installed) U
NOM
6042 G transformer Secondary voltage of the G voltage transformer (if installed) U
NOM
6051 BB transformer Primary voltage of the BB voltage transformer (if installed) U
NOM
6052 BB transformer Secondary voltage of the BB voltage transformer (if installed) U
NOM
6053 BB nom. voltage Phase-phase voltage of the busbar U
NOM
The controller has two sets of BB transformer settings, which can be enabled individually in
this measurement system.
4.4 Applications
4.4.1 Applications and genset modes
This section about applications is to be used for reference using the particular genset mode as
starting point. It is not suitable for reading from beginning to end.
The unit can be used for the applications listed in the table below.
Application Comment
Automatic Mains Failure (no back sync.) CGC 413
Island operation CGC 412/CGC 413
Load takeover CGC 413
Genset mode Running mode
Auto Test Man Block
Automatic Mains Failure (no back sync.) X X X X
Island operation X X X X
Load takeover X X X X
For a general description of the available running modes, please refer to the chapter "Running
mode description".
4.4.2 Application design
The application is designed through the utility software. Please select configuration.
CGC 400 DRH 4189340786 UK
Functional descriptions
DEIF A/S Page 13 of 96