7.23.1 Standard texts
Condition Comment
BLOCK Block mode is activated
SIMPLE TEST Test mode is activated
FULL TEST
SIMPLE TEST ###.#min Test mode activated and test timer counting down
FULL TEST ###.#min
ISLAND MAN Genset stopped or running and no other action taking
place
READY ISLAND AUTO Genset stopped in Auto
ISLAND ACTIVE Genset running in Auto
AMF MAN Genset stopped or running and no other action taking
place
READY AMF AUTO Genset stopped in Auto
AMF ACTIVE Genset running in Auto
LOAD TAKEOVER MAN Genset stopped or running and no other action taking
place
READY LTO AUTO Genset stopped in Auto
LTO ACTIVE Genset running in Auto
DG BLOCKED FOR
START
Generator stopped and active alarm(s) on the genera-
tor
GB ON BLOCKED Generator running, GB open and an active "Trip GB"
alarm
SHUTDOWN OVER-
RIDE
The configurable input is active
ACCESS LOCK The configurable input is activated, and the operator
tries to activate one of the blocked keys
GB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is log-
ged in the event log
MB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is log-
ged in the event log
IDLE RUN The "Idle run" function is active. The genset will not
stop until a timer has expired
IDLE RUN ###.#min The timer in the "Idle run"’ function is active
START PREPARE The start prepare relay is activated
START RELAY ON The start relay is activated
START RELAY OFF The start relay is deactivated during the start se-
quence
MAINS FAILURE Mains failure and mains failure timer expired
CGC 400 DRH 4189340786 UK Additional functions
DEIF A/S Page 85 of 96