4.8.5 Stop sequence
The drawings illustrate the stop sequence.
t
COOL
t
stop
Run coil
Stop sequence
Cooling down time
Run coil
Running feedback
Sequence initiated
t
COOL
t
stop
Stop coil
Stop sequence
Cooling down time
Stop coil
Running feedback
Sequence initiated
The stop sequence will be activated if a stop command is given. The stop sequence includes the cooling
down time if the stop is a normal or controlled stop.
CGC 400 DRH 4189340786 UK
Functional descriptions
DEIF A/S Page 38 of 96