7.20 Multi-inputs
7.20.1 Multi-inputs
The CGC 412 unit has three multi-inputs which can be configured to be used as the following input types:
1. 4-20 mA
2. Pt100
3. Pt1000
4. RMI oil
5. RMI water
6. RMI fuel
7. Binary
The CGC 413 has two extra multi-inputs. These two extras cannot be used in the sequences like during the
startup of the engine (Oil P, etc....).
The multi-inputs 58 and 59 can be configured in a way to give two alarm leves per input.
The configuration of the function of each for multi-inputs is done in the USW tab in the PC tool. The channel
numbers used are following the below table.
Input number Channel
Multi-input 6 10980
Multi-input 7 10990
Multi-input 8 11000
Multi-input 58 11300
Multi-input 59 11310
The function of the multi-inputs can only be configured in the PC utility software.
For each input, two alarm levels are available, the menu numbers of the alarm settings for each multi-input is
controlled by the configured input type as seen in the following table.
Input type Multi-input 6 Multi-input 7 Multi-input 8 Multi-input 58 Multi-input 59
4-20 mA 4120/4130 4250/4260 4380/4390 4740/4750 4770/4780
Pt100 4160/4170 4290/4300 4420/4430 4740/4750 4770/4780
Pt1000 4160/4170 4290/4300 4420/4430 4740/4750 4770/4780
RMI oil 4180/4190 4310/4320 4440/4450 4740/4750 4770/4780
RMI water 4200/4210 4330/4340 4460/4470 4740/4750 4770/4780
RMI fuel 4220/4230 4350/4360 4480/4490 4740/4750 4770/4780
Binary 3400 3410 3420 4740 4770
Only one alarm level is available for the digital input type.
When the multi-inputs 58 and 59 are configured as binary inputs, and the wirebreak alarm occurs, it will use
channels under main menu 4000 (normally reserved for analogue).