Start Stop
RPM
300
1500
t
The oil pressure alarm (RMI oil) will be enabled during idle run if set to "ON".
7.10.4 Inhibit
The alarms that are deactivated by the inhibit function are inhibited in the usual manner, except for the oil
pressure alarms; RMI oil 6,7 and 8 which are active during "idle run" as well.
7.10.5 Running signal
The running feedback must be activated when the genset is running in idle mode.
7.10.6 Idle speed flowcharts
The flowcharts illustrate the starting and stopping of the genset by use of the inputs "temp control" and "low
speed".
CGC 400 DRH 4189340786 UK Additional functions
DEIF A/S Page 61 of 96