EasyManua.ls Logo

Deif CGC 400 - 7 Additional Functions; Start Functions; Digital Feedbacks

Deif CGC 400
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. Additional functions
7.1 Start functions
7.1.1 Start functions
The controller will start the genset when the start command is given. The start sequence is deactivated when
the remove starter event occurs or when the running feedback is present.
The reason for having two possibilities to deactivate the start relay is to be able to delay the alarms with run
status.
If it is not possible to activate the run status alarms at low revolutions, the remove starter function must be
used.
An example of a critical alarm is the oil pressure alarm. Normally, it is configured according to the shutdown
fail class. But if the starter motor has to disengage at 400 RPM, and the oil pressure does not reach a level
above the shutdown setpoint before 600 RPM, then the genset would shut down if the specific alarm was ac-
tivated at the preset 400 RPM. In that case, the running feedback must be activated at a higher number of
revolutions than 600 RPM.
t
RPM
Oil pressure
400
1000
RPM
600
Running
Remove starter
7.1.2 Digital feedbacks
If an external running relay is installed, the digital control inputs for running detection or remove starter can be
used.
Running feedback
When the digital running feedback is active, the start relay is deactivated, and the starter motor will be disen-
gaged.
CGC 400 DRH 4189340786 UK
Additional functions
DEIF A/S Page 45 of 96

Table of Contents

Other manuals for Deif CGC 400

Related product manuals