Selections for alarm inhibit:
Function Description
Inhibit 1 M-Logic outputs: Conditions are programmed in M-Logic
Inhibit 2
Inhibit 3
GB ON (TB ON) The generator breaker is closed
GB OFF (TB ON) The generator breaker is open
Run status Running detected and the timer in menu 6160 expired
Not run status Running not detected or the timer in menu 6160 not expired
Generator voltage > 30% Generator voltage is above 30% of nominal
Generator voltage < 30% Generator voltage is below 30% of nominal
MB ON The mains breaker is closed
MB OFF The mains breaker is open
The timer in 6160 is not used if binary running feedback is used.
Inhibit of the alarm is active as long as one of the selected inhibit functions is active.
Example: