Table 24 Maximum vibration specifications
Maximum vibration Specifications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all operation
orientations).
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides
tested).
The table below shows the maximum shock specifications during operations and storage:
Table 25 Maximum shock specifications
Maximum shock Specifications
Operating Six consecutively executed shock pulses in the
positive and negative x, y, and z axes of 6 G for up
to 11 ms.
Storage Six consecutively executed shock pulses in the
positive and negative x, y, and z axes (one pulse on
each side of the appliance) of 71 G for up to 2 ms.
The table below shows the maximum altitude specifications during operations and storage.
Table 26
Maximum altitude specifications
Maximum altitude Specifications
Operating 3048 m (10,000 ft)
Storage 12,000 m (39,370 ft)
The table below shows the operating temperature de-rating specifications:
Table 27
Operating temperature de-rating specifications
Operating temperature de-rating Specifications
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m
(1°F/547 ft) above 950 m (3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m
(1°F/319 ft) above 950 m (3,117 ft).
40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m
(1°F/228 ft) above 950 m (3,117 ft).
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from
particulates and gaseous contamination. If the levels of particulates or gaseous pollution exceed
the specified limitations and result in equipment damage or failure, you may need to rectify the
environmental conditions. Re-mediation of environmental conditions is the responsibility of the
customer.
Air filtration specification: Data center air filtration as defined by ISO Class 8 per ISO 14644-1
shpuld have a 95% upper confidence limit. Note: This condition applies only to data center
environments. Air filtration requirements do not apply to IT equipment designed to be used outside
Technical specifications
Dell EMC VxRail Appliances on PowerEdge Servers E Series Owner's Manual 27