Expanded operating temperature
When the appliance is in continuous operation, the expanded operating temperature ranges from
5°C to 40°C at 5% to 85% RH with 29°C dew point. Outside the standard operating temperature
(10°C to 35°C), the appliance can operate continuously in temperatures as low as 5°C and as high
as 40°C. For temperatures between 35°C and 40°C, de-rate maximum allowable temperature by
1°C per 175 m above 950 m (1°F per 319 ft). When the appliance is operating at < 1% of annual
operating hours, the expanded operating temperature is –5°C to 45°C at 5% to 90% RH with
29°C dew point. NOTE: Outside the standard operating temperature (10°C to 35°C), the
appliance can operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating
hours. For temperatures between 40°C and 45°C, de-rate maximum allowable temperature by 1°C
per 125 m above 950 m (1°F per 228 ft).
Table 30 Expanded operating temperature specifications
Expanded operating temperature Specifications
Continuous operation 5°C to 40°C at 5% to 85% RH with 29°C
dew point.
Note: Outside the standard operating
temperature (10°C to 35°C), the
appliance can operate continuously in
temperatures as low as 5°C and as high
as 40°C.
For temperatures between 35°C and 40°C,
de-rate maximum allowable temperature by
1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours –5°C to 45°C at 5% to 90% RH with 29°C
dew point.
Note: Outside the standard operating
temperature (10°C to 35°C), the
appliance can operate down to –5°C or
up to 45°C for a maximum of 1% of its
annual operating hours.
For temperatures between 40°C and 45°C,
de-rate maximum allowable temperature by
1°C per 125 m above 950 m (1°F per 228 ft).
Note: When operating in the expanded temperature range:
l
The performance of the appliance may be impacted.
l
The ambient temperature warnings may be reported in the System Event Log.
Expanded operating temperature restrictions
l
Do not perform a cold startup below 5°C.
l
The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
l
Redundant power supply units are required.
l
Non-EMC qualified peripheral cards and/or peripheral cards greater than 25 W are not
supported.
Technical specifications
Dell EMC VxRail Appliances on PowerEdge Servers E Series Owner's Manual 29