Dell PowerEdge M630 - Particulate and Gaseous Contamination Specifications

Dell PowerEdge M630
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
Table 11. Relative humidity
specifications
Relative humidity
Specifications
Storage 5% to 95% RH with 33°C (91°F) maximum dew point.
Atmosphere must be noncondensing always.
Operating 10% to 80% Relative Humidity with 29°C (84.2°F) maximum
dew point.
Table 12. Maximum vibration
specifications
Maximum vibration
Specifications
Operating 0.26 Grms at 5 Hz to 350 Hz (all operation orientations).
Storage 1.88 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested).
Table 13. Maximum shock
specifications
Maximum shock
Specifications
Operating Six consecutively run shock pulses in the positive and negative
x, y, and z axes of 40 G for up to 2.3 ms.
Storage
Six consecutively run shock pulses in the positive and negative
x, y, and z axes (one pulse on each side of the system) of 71 G
for up to 2 ms.
Table 14. Maximum altitude
specifications
Maximum altitude
Specifications
Operating 3048 m (10,000 ft).
Storage 12,000 m (39,370 ft).
Table 15. Operating temperature derating
specifications
Temperature Specifications
Up to 35 °C (95 °F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft)
above 950 m(3,117 ft).
35
°C
to
40
°C
(95
°F
to
104
°F)
Ma
ximum
t
emper
a
tur
e
is
r
educed
by
1°C
/175
m
(
1°F
/
3
19
ft
)
above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft)
above 950 m(3,117 ft).
Particulate and gaseous contamination
specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous
contamination. If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or
failure, you may need to rectifythe environmental conditions. Remediation of environmental conditions is the responsibility of t h e
customer.
Table 16. Particulate contamination
specifications
Particulatecontamination
Specifications
Air filtration
Datacenterairfiltrationasdefinedby ISOClass 8 per ISO
14644-1with a 95% upper confidence limit.