42 | Specifications
www.dell.com | support.dell.com
DC Power Requirements
IEEE Standards
The S4810 complies with the following IEEE standards:
802.3ae 10 Gigabit Ethernet
802.3ab 1000Base-T
802.1p L2 Prioritization
802.1Q VLAN Tagging, Double VLAN Tagging (Q in Q), GVRP
802.1s Multiple Spanning Tree Protocol
802.1w Rapid Spanning Tree Protocol
802.3ad Link Aggregation with LACP
802.1D Bridging, GARP, GMRP
802.3x Flow Control
802.1ac Frame Extension for VLAN Tagging
802.1x Port Based Network Access Control
Agency Compliance
Network Equipment Building Systems (NEBS) Compliance
Use shielded cables for ports 0 - 43. You must ground the shields at both ends.
Use only reverse airflow configurations in a NEBS-compliant installation. Use only AC supply
S55-PWR-AC-R, DC supply S55-PWR-DC-R and Fan Only S55-FAN-R, Systems S55-44T-AC-R and
S55-44T-DC-R.
Fit the power supplies and fan modules with filter kits (S55-PWR-FLTR). You must replace the fan
filters on a regular basis.
Use this equipment with an external, second-level 6kV lightning Surge Protective Device (SPD) at the
AC input of the building.
Parameter Specifications
Nominal input voltage 36 to 72 VDC
Maximum power supply input current 2.8A @ 36 VDC
1.85 A @ 72 VDC
Maximum system power input 360 W