Chapter 9 Troubleshooting
9-39
9_
Error Code Description Corrective action
16#001A
The contents of the system backup file
(.dup file) are incorrect.
Create the system backup file again.
16#0033
The communication setting of COM1 is
incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0034
The setting of the station address of
COM1 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0035
The setting of the communication type of
COM1 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0038
The communication setting of COM2 is
incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0039
The setting of the station address of
COM2 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#003A
The setting of the communication type of
COM2 is incorrect. (SM9)
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
16#0066
An error occurs when the system is
backed up.
1. Check whether the memory card is normal, and
whether the capacity of the memory card is large
enough.
2. Retry the backup procedure. If the error still occurs,
please contact the factory.
16#0067
The size of the PLC parameters restored
exceeds the size of the PLC parameters
of the CPU module.
The error code is appeared to indicate alarm only.
16#2000
There is no END in the program in the
PLC. (SM5)
1. Compile the program again, and download the
program again.
2. Reinstall ISPSoft, compile the program again, and
download the program again.
16#2001
The program is incorrect. There is a
syntax error.
Check the program, compile the program again, and
download the program again.

Table of Contents

Other manuals for Delta AH Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AH Series and is the answer not in the manual?

Delta AH Series Specifications

General IconGeneral
BrandDelta
ModelAH Series
CategoryController
LanguageEnglish

Related product manuals