54
Amplon RT Series
z
Battery
Setup Item Selectable Value Default Value
Automatic Battery Test
No test/ Daily/ Weekly/
Biweekly/ Monthly
No test
Deep Discharge Test
20-90% (one step: 10%) 90%
Low Battery
Warning Capacity
0-95%
(one step: 5%)
10%
Warning of
Remaining Time
0-60mins
(one step: 1min)
2mins
Runtime Limitation
Disable/ 1/ 2/ 3…./ 240
(one step: 1min)
Disable
Charge Mode
2-stage/ 3-stage 2-stage
Float Charging
Voltage
Auto/ Customize
9FHOO
RQHVWHS9
Auto
Internal Charging
Current
For 5K/ 6K: 1/ 2/ 3/ 4/ 5/ 6/ 7/ 8
For 8K/ 10K: 1.5/ 2/ 3/ 4/ 5/ 6
1A (5K/ 6K)
1.5A (8K/ 10K)
External Battery Type *
Standard battery pack/
Customer own batt. pack
External Battery
Capacity
Standard battery pack:
Part Number Quantity
Customer own batt. pack:
%DWWHU\9ROWDJH&DSDFLW\
Install date
YYYY/ MM/ DD
NOTE :
*
When the
External Battery Type
is set as
Standard battery pack
, you
need to configure the
Part Number
and the
Quantity
of the standard
battery pack(s).

Other manuals for Delta Amplon RT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Amplon RT Series and is the answer not in the manual?

Delta Amplon RT Series Specifications

General IconGeneral
BrandDelta
ModelAmplon RT Series
CategoryUPS
LanguageEnglish

Related product manuals