ASDA-B2  Chapter 7 Parameters 
Revision May, 2018  7-53 
P2-06    KVI 
Speed Integral Compensation 
Address: 020CH 
020DH 
 
Operation 
Interface: 
Panel/Software   Communication  
Related Section:   
6.3.6 
 
 
Default: 100 
 
Control 
Mode: 
ALL 
 
Unit: rad/s 
 
Range: 0 ~ 1023 
 
Data Size: 16-bit 
 
Format: Decimal 
Settings: Increasing the value of speed integral compensation can enhance 
speed response and diminish the deviation of speed control. 
However, if the value is set too big, it would easily cause 
resonance and noise. 
 
P2-07    KVF 
Speed Feed Forward Gain 
Address: 020EH 
020FH 
 
Operation 
Interface: 
Panel/Software   Communication  
Related Section:   
6.3.6 
 
 
Default: 0 
 
Control 
Mode: 
ALL 
 
Unit: % 
 
Range: 0 ~ 100 
 
Data Size: 16-bit 
 
Format: Decimal 
Settings: When the speed control command runs smoothly, increasing the 
gain value can reduce the speed command error. If the command 
does not run smoothly, decreasing the gain value can reduce the 
mechanical vibration during operation. 
 
P2-08■    PCTL 
Special Parameter Write-in 
Address: 0210H 
0211H 
 
Operation 
Interface: 
Panel/Software   Communication  
Related Section: N/A 
 
 
Default: 0 
 
Control 
Mode: 
ALL 
 
Unit: N/A 
 
Range: 0 ~ 65535 
 
Data Size: 16-bit 
 
Format: Decimal