Chapter 11 Summary of Parameter SettingsCP2000
11-6
Pr. Parameter Name Settings Range Default
00-26 Max. user defined value
0: No function
0–65535 (when Pr.00-25 set to no decimal place)
0.0–6553.5 (when Pr.00-25 set to 1 decimal place)
0.00–655.35 (when Pr.00-25 set to 2 decimal
places)
0.000–65.535 (when Pr.00-25 set to 3 decimal
places)
0
00-27 User-defined value Read only
Read
Only
00-28
Switching from Auto mode to Hand
mode
bit0: Sleep function control bit
0: Cancel sleep function
1: Sleep function and Auto mode are the same
bit1: Control bit unit
0: Displaying unit in Hz
1: Same unit as the Auto mode
bit2: PID control bit
0: Cancel PID control
1: PID control and Auto mode are the same
bit3: Frequency source control bit
0: Frequency source set up by
parameter, if the
multi-step speed is activated, then
multi-speed has the priority.
1: Frequency command set up by
Pr.00-30,
regardless of whether the multi-step speed
is activated.
00-29 LOCAL / REMOTE selection
0: Standard HOA function
1: Switching Local / Remote, the drive stops
2: Switching Local / Remote, the drive runs as the
REMOTE setting for frequency and operation
status
3: Switching Local / Remote, the drive runs as the
LOCAL setting for frequency and operation status
4: Switching Local / Remote, the drive runs as
LOCAL setting when switched to Local and runs
as REMOTE setting when switched to Remote for
frequency and operation status.
0
00-30
Master frequency command source
(HAND)
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP / DOWN terminal
6: CANopen communication card
8: Communication card (no CANopen card)
0
00-31
Operation command source
(HAND)
0: Digital keypad
1: External terminals
2: RS-485 serial communication
3: CANopen communication card
5: Communication card (no CANopen card)
0
00-32 Digital keypad STOP function
0: STOP key disable
1: STOP key enable
0

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals