Chapter 11 Summary of Parameter SettingsCP2000
11-39
12 PUMP Parameters
Pr. Parameter Name Setting Range Default
12-00 Circulation Control
0: No operation
1: Fixed time circulation (by time)
2: Fixed quantity circulation
3: Fixed quantity control
4: Fixed time circulation + fixed quantity circulation
5: Fixed time circulation + fixed quantity control
0
12-01
Number of Motors to be
connected
1–8 1
12-02
Operating time for each motor
(minutes)
0–65500 min. 0
12-03
Delay time due to the
acceleration (or the increment )
at motor switching (seconds)
0.0–3600.0 sec. 1.0
12-04
Delay time due to the
deceleration ( or the decrement)
at motor switching (seconds)
0.0–3600.0 sec. 1.0
12-05
Delay time due to fixed quantity
circulation at motor switching
(seconds)
0.0–3600.0 sec. 10.0
12-06
Frequency when switching
motors at fixed quantity
circulation (Hz)
0.00–599.00 Hz 60.0
12-07
Action when fixed 1uantity
circulation breaks down
0: Turn off all output
1: Motors powered by mains electricity continues to
operate
0
12-08
Frequency for stopping auxiliary
motor (Hz)
0.00–599.00 Hz 0.00
12-09
Fixed quantity circulation output
delay
1.0–3600.0 sec. 1.0
12-10
Motor 1 operation record
(min./sec.)
Read only
Read
Only
12-11 Motor 1 operation record (hour) Read only
Read
Only
12-12
Motor 2 operation record
(min./sec.)
Read only
Read
Only
12-13 Motor 2 operation record (hour) Read only
Read
Only
12-14
Motor 3 operation record
(min./sec.)
Read only
Read
Only
12-15 Motor 3 operation record (hour) Read only
Read
Only
12-16
Motor 4 operation record
(min./sec.)
Read only
Read
Only
12-17 Motor 4 operation record (hour) Read only
Read
Only