Chapter 12 Description of Parameter SettingsCP2000
12.1-00-13
User-Defined Value
Default: Read only
Settings Read only
Pr.00-27 displays the user-defined value when Pr.00-26 is not set to 0.
The user-defined value is valid when Pr.00-20 (frequency source) is set to the digital keypad or to
RS-485 communication.
Switching from Auto mode to Hand mode
Default: 0
Settings
bit0: Sleep function control bit
0: Sleep function control bit
1: Sleep function and Auto mode are the same
bit1: Control bit unit
0: Displaying unit in Hz
1: Same unit as the Auto mode
bit2: PID control bit
0: Cancel PID control
1: PID control and Auto mode are the same.
bit3: Frequency source control bit
0: Frequency source set up by parameter, if the multi-step speed is
activated, then multi-step speed has the priority.
1: Frequency command set up by Pr.00-30, regardless of whether the
multi-step speed is activated.
LOCAL / REMOTE Selection
Default: 0
Settings 0: Standard HOA function
1: Switch Local / Remote, the drive stops
2: Switch Local / Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Switch Local / Remote, the drive runs as the LOCAL setting for frequency
and operation status
4: Switch Local / Remote, the drive runs as LOCAL setting when switched to
Local, and runs as REMOTE setting when switch to Remote for frequency
and operation status.
The default for Pr.00-29 is 0 (standard Hand-Off-Auto function). Set the AUTO frequency and
operation source with Pr.00-20 and Pr.00-21. Set the HAND frequency and operation source with
Pr.00-30 and Pr.00-31. Select or switch AUTO / HAND mode by using the digital keypad
KPC-CC01 or setting the multi-function input terminal MIx= 41, 42.
When you set the external terminal (MI) to 41 and 42 (AUTO / HAND mode), Pr.00-29=1, 2, 3, 4
are disabled. The external terminal has the highest command priority, and Pr.00-29 functions in
standard HOA mode.

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals