Chapter 12 Description of Parameter SettingsCP2000
12.1-08-9
Wake-up Integral Limit
Default: 50.0
Settings 0.0200.0%
The wake-up integral limit for the drive prevents suddenly running at high speed when the drive
wakes up. The wake-up integral frequency limit = (Pr.01-00 × Pr.08-19%)
Reduces the reaction time from sleep to wake-up.
Enable PID to Change the Operation Direction
Default: 0
Settings 0: Operation direction cannot be changed
1: Operation direction can be changed
Wake-up Delay Time
Default: 0.00
Settings 0.00600.00 sec.
Refer to Pr.08-18 for more information.
There are three scenarios for sleep and wake-up frequency. Refer to following explanations:
1. Frequency Command (PID is not in use, Pr.08-00=0, only works in VF mode)
When the output frequency the sleep frequency, and the drive reaches the preset sleep
time, then the drive is in sleep mode.
When the frequency command reaches the wake-up frequency, the drive starts to count the
wake-up delay time. When the drive reaches the wake-up delay time, the drive begins
acceleration time to reach the frequency command value.
Sleep Mode Diagram

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals