Chapter 12 Description of Parameter SettingsCP2000
12.1-09-13
Block Transfer 8
Block Transfer 9
Block Transfer 10
Block Transfer 11
Block Transfer 12
Block Transfer 13
Block Transfer 14
Block Transfer 15
Block Transfer 16
Default: 0000
Settings 0–FFFFh
There is a group of block transfer parameters available in the AC motor drive (Pr.09-11 to
Pr.09-26). Using communication code 03H, you can store the parameters (Pr.09-11–Pr.09-26)
that you want to read.
For example: according to the Address List (as shown in the table below), Pr.01-42 is shown as
012A. Set Pr.09-11 to 012Ah (the minimum voltage of Pr.01-42 M2 is 2.0 V), and use Pr.09-11
(communication address 090B) to read the communication parameter, the read value is 2.0.
AC motor drive
parameters
GGnnH
GG is the parameter group, nn is the parameter number; for
example, the address of Pr.04-10 is 040AH.
Communication Decoding Method
Default: 1
Settings 0: Decoding Method 1 (20xx)
1: Decoding Method 2 (60xx)
Decoding Method 1 Decoding Method 2
Source of
Operation
Control
Digital Keypad Digital keypad controls the drive action regardless of decoding method 1 or 2.
External Terminal External terminal controls the drive action regardless of decoding method 1 or 2.
RS-485 Refer to address: 2000h–20FFh Refer to address: 6000h–60FFh
CANopen Refer to index: 2020-01h–2020-FFh Refer to index: 2060-01h–2060-FFh
Communication Card Refer to address: 2000h–20FFh Refer to address: 6000h–60FFh
PLC PLC commands controls the drive action regardless of decoding method 1 or 2.
Internal Communication Protocol
Default: 0
Settings 1: BACnet
0: Modbus 485
-1: Internal Communication Slave 1
-2: Internal Communication Slave 2
-3: Internal Communication Slave 3
-4: Internal Communication Slave 4
-5: Internal Communication Slave 5

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals