Chapter 15 CANopen OverviewCP2000
15-24
ID
No.*
Display Fault code
Description
CANopen
fault register
(bit0–7)
CANopen
fault code
51
0033H
External Base Block; when the
multi-function input terminal (B.B.) is
active, the AC motor drive stops
output
5 9000H
52
0034H
Keypad is locked after you enter the
wrong password three times
5 FF26H
54
0036H
Modbus function code error (illegal
function code)
4 7500H
55
0037H
Modus data address error [Illegal
data address (00H–254H)]
4 7500H
56
0038H
Modbus data error (illegal data value)
4 7500H
57
0039H
Modbus communication error (data is
written to read-only address)
4 7500H
58
003AH
Modbus transmission time-out.
5 7500H
60
003CH
Brake resistor fault
4 7110H
61
003DH
Y-connection / Δ-connection switch
error
2 3330H
62
003EH
Energy regeneration when
decelerating
2 FF27H
63
003FH
Motor slip exceeds Pr.05-26 and
Pr.05-27 setting
7 FF28H

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit

Related product manuals