Chapter 4 WiringCP2000
4-2
After removing the front cover, please check if the power and control terminals are clearly noted.
Please read following precautions to avoid wiring mistakes.
It is crucial to cut off the AC motor drive power before any wiring installation are
made. A charge may still remain in the DC BUS capacitors with hazardous voltages
even if the power has been turned off. Therefore, it is suggested for users to
measure the remaining voltage by DC voltage meter before wiring. For your
personnel safety, please do not perform any wiring before the voltage drops to a
safe level < 25 V
DC
. Wiring installation with remaining voltage condition may cause
sparks and short circuit.
Only qualified personnel familiar with AC motor drives is allowed to perform
installation, wiring and commissioning. Make sure the power is turned off before
wiring to prevent electric shock.
Make sure that power is only applied to the R/L1, S/L2, and T/L3 terminals. Failure
to comply may result in damage to the equipment. The voltage and current should
lie within the range as indicated on the nameplate (Chapter 1-1 Nameplate
Information).
All the units must be grounded directly to a common ground terminal to prevent
lightning strike or electric shock.
Please make sure to fasten the screw of the main circuit terminals to prevent
sparks which is made by the loose screws due to vibration.
When wiring, please choose the wires with specification that complies with local
regulation for your personnel safety.
Check following items after finishing the wiring:
1. Are all connections correct?
2. Any loosen wires?
3. Any short-circuits between the terminals or to ground?

Table of Contents

Other manuals for Delta CP2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta CP2000 Series and is the answer not in the manual?

Delta CP2000 Series Specifications

General IconGeneral
Output Voltage0 ~ Input Voltage
Communication InterfaceRS-485
Storage Temperature-20°C to 60°C
Input Voltage200-240V AC, 380-480V AC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit