2. Programming Concepts
2-73
Function Group
Output clear signals when ZRN is completed
Number
M1346
Contents:
When M1346 = ON, PLC will output clear signals when ZRN is completed. The clear signals to Y0,
Y1 will be sent by Y4 for 20ms, and the clear signals to Y2, Y3 will be sent by Y5 for 20ms.
Function Group
PLC LINK
Number
M1350-M1356, M1360-M1439, D1355-D1370, D1399, D1415-D1465, D1480-
D1991
Contents:
1. PLC LINK supports COM2 (RS-485) with communication of up to 16 slaves and access of up
to 50 words. (DVP-12SE V1.6 and DVP-26SE V2.0 can connect to up to 32 slaves, and
read/write up to 100 words.)
2. Special D and special M corresponding to Connection ID1~ Connection ID8: (M1353 = OFF,
access available for only 16 words)
MASTER PLC
CONNECTION
ID 1
CONNECTION
ID 2
CONNECTION
ID 3
CONNECTION
ID 4
CONNECTION
ID 5
CONNECTION
ID 6
CONNECTION
ID 7
CONNECTION
ID 8
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Special D registers for storing the read/written 16 data (Auto-assigned)
D1480
D1495
D1496
D1511
D1512
D1527
D1528
D1543
D1544
D1559
D1560
D1575
D1576
D1591
D1592
D1607
D1608
D1623
D1624
D1639
D1640
D1655
D1656
D1671
D1672
D1687
D1688
D1703
D1704
D1719
D1720
D1735
Data length to be read/written for connections (Max 16 pieces of data; 0: no reading/writing)
D1434
D1450
D1435
D1451
D1436
D1452
D1437
D1453
D1438
D1454
D1439
D1455
D1440
D1456
D1441
D1457
Starting address of the Connection to be read, written or connected.*
D1355
D1415
D1356
D1416
D1357
D1417
D1358
D1418
D1359
D1419
D1360
D1420
D1361
D1421
D1362
D1422
M1355 = ON, Connection status is user-defined. Activate the Connection manually with M1360~M1367.
M1355 = OFF, Connection status is auto-detected. Monitor if the connection is established and activated with M1360~M1367
M1360
M1361
M1362
M1363
M1364
M1365
M1366
M1367
Communication status of Connection ID#1-8 on PLC LINK (ON: communicating)
M1376
M1377
M1378
M1379
M1380
M1381
M1382
M1383
Error flag for errors occurred when reading and writing (ON = normal; OFF = error)
M1392
M1393
M1394
M1395
M1396
M1397
M1398
M1399
“Reading completed” flag (System resets to OFF after reading is complete on one module.)
M1408
M1409
M1410
M1411
M1412
M1413
M1414
M1415
“Writing completed” flag (System resets to OFF after writing is complete on one module.)
M1424
M1425
M1426
M1427
M1428
M1429
M1430
M1431
Slave PLC*
CONNECTION
ID 1
CONNECTION
ID 2
CONNECTION
ID 3
CONNECTION
ID 4
CONNECTION
ID 5
CONNECTION
ID 6
CONNECTION
ID 7
CONNECTION
ID 8
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
D100
D115
D200
D215
D100
D115
D200
D215
D100
D115
D200
D215
D100
D115
D200
D215
D100
D115
D200
D215
D100
D115
D200
D215
D100
D115
D200
D215
D100
D115
D200
D215
3. Special D and special M corresponding to Connection ID9~ Connection ID16: (M1353 = OFF,
access available for only 16 words)
MASTER PLC
CONNECTION
ID 9
CONNECTION
ID 10
CONNECTION
ID 11
CONNECTION
ID 12
CONNECTION
ID 13
CONNECTION
ID 14
CONNECTION
ID 15
CONNECTION
ID 16
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Read
out
Write
in
Special D registers for storing the read/written 16 pieces of data (Auto-assigned)
D1736
D1751
D1752
D1767
D1768
D1783
D1784
D1799
D1800
D1815
D1816
D1831
D1832
D1847
D1848
D1863
D1864
D1879
D1880
D1895
D1896
D1911
D1912
D1927
D1928
D1943
D1944
D1959
D1960
D1975
D1976
D1991
Data length to be read/written for connections (Max 16 pieces of data; 0: no reading/writing)
D1442
D1458
D1443
D1459
D1444
D1460
D1445
D1461
D1446
D1462
D1447
D1463
D1448
D1464
D1449
D1465