DVP-ES2/EX2/EC5/SS2/SA2/SX2/SE&TP Operation Manual - Programming
Starting address of the Connection to be read, written or connected.*
M1355 = ON, Connection status is user-defined. Activate the Connection manually with M1368~M1375.
M1355 = OFF, Connection status is auto-detected. Monitor if the connection is established and activated with M1368~M1375.
Communication status of Connection ID#9-16 on PLC LINK (ON: communicating)
Error flag for errors occurred when reading or writing on Connection ID#9-16(ON = normal; OFF = error)
Reading complete on PLC LINK Connection ID#9-16 (System resets to OFF after reading is complete on one module.)
Writing complete on PLC LINK connection ID#9-16 (System resets to OFF after writing is complete on one module.)
│
│
│
│
│
│
│
│
│
│
│
│
│
│
│
│
4. Special D and special M corresponding to Connection ID1~ID8: (M1353 = ON, access
available for up to 50 words) (DVP-12SE V1.6 and DVP-26SE V2.0 supports 100 words at
most.)
M1353 = ON, enable access up to 50 words.
The user can specify the starting register for storing the read/written data in registers below.
M1356 = ON, the user can specify the station number of Connection ID1~ID8 in D1900~D1907
Data length to be read/written for connections (Max 50 pieces of data; 0: no reading/writing)
Starting address of the Connection to be read, written or connected.*
M1355 = ON, Connection status is user-defined. Activate the Connection manually with M1360~M1367.
M1355 = OFF, Connection status is auto-detected. Monitor if the connection is established and activated with M1360~M1367.
Communication status of Connection ID#1-8 on PLC LINK (ON: communicating)
Error flag for errors occurred when reading or writing on Connection ID#1-8 (ON = normal; OFF = error)
Reading complete on PLC LINK Connection ID#1-8 (System resets to OFF after reading is complete on one module.)
Writing complete on PLC LINK connection ID#1-8 (System resets to OFF after writing is complete on one module.)
│
│
│
│
│
│
│
│
│
│
│
│
│
│
│
│