EasyManua.ls Logo

Delta DVP-EX2 - Page 484

Delta DVP-EX2
1006 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Instruction Set
3-363
Program Example 3: COM2 (RS-485), Function Code H03 (The function code H04 is the same
as the function code H03.)
1. Function code K3 (H03): read multiple Word devices. Up to 16 words can be read. For COM2
ASCII mode, only 8 words can be read.
2. For ASCII or RTU mode, PLC COM2 stores the data to be sent in D1256~D1295, converts the
received data in registers starting from S, and stores the converted 16-bit data in D1296 ~
D1311.
3. Take the connection between PLC (PLC COM2) and VFD-B for example, the tables below
explains the status when PLC reads status of VFD-B. (M1143 = OFF, ASCII Mode) (M1143
= ON, RTU Mode)
H87
MOV
M1002
D1120
SET
M1120
K100
MOV
D1129
RST
M1127
Set communication protocol as 9600, 8, E, 1
Retain communication protocol
Set communication timeout as 100ms
MODRW K3K1
X0
H2100 D0 K6
Connection device
address: K1
Function code: K3
read multiple words
Data address: H2100
Data storing register
Data length(word)
Processing received data
ASCII mode : The received ASCII data is stored in registers starting from D0
and PLC converts the ASCII data to Hex value and stores them in
D1296~D1301 automatically.
RTU mode : The received data is stored in registers starting from D0 in Hex value.
Reset M1127
M1127
SET
X0
M1122
Sending request
M1143 = OFF
ASCII mode
RST
M1143
M1143 = ON
RTU mode
SET
M1143
Receiving completed
ASCII mode (M1143 = OFF):
When X0 = ON, MODRW instruction executes the function specified by Function Code 03
PLC VFD-B, PLC sends: “01 03 2100 0006 D5”
VFD-B PLC, PLC receives: “01 03 0C 0100 1766 0000 0000 0136 0000 3B”
Registers for data to be sent (sending messages)

Table of Contents

Related product manuals