Chapter 5 Parameters|VFD-B-P Series
Revision April 2009, SW V1.00 5-69
16 CPU WRITE failure (CF2)
17 Reserved
18 Motor over load (oL2)
19 Auto accel/decel failure (CFA)
20 Software/password protection (codE)
21 Emergency stop (EF1)
22 Phase-Loss (PHL)
23 Preliminary count value attained, EF active (cEF)
24 Under-current (Lc)
25 Analog feedback signal error (AnLEr)
26 PG feedback signal error (PGErr)
06 - 12 Under-Current Detection Level Unit: 1
Settings 00 ~ 100% Factory Setting: 00
00 Disabled
06 - 13 Under-Current Detection Time Unit: 0.1
Settings 0.1~ 3600.0 sec Factory Setting: 10.0
06 - 14 Under-Current Detection Mode
Factory Setting: 00
Settings 00 Warn and keep operating
01 Warn and ramp to stop
02 Warn and coast to stop
03 Warn, after coast to stop, restart (delay 06-15 setting time)
06 - 15 Under-Current Detection Restart Delay Time Unit: 1
Settings 1~600 min Factory Setting: 10
If output current is lower than the setting Pr.06-12 for a time that exceeds Pr.06-13 setting
during operation, the AC drive will warn per Pr.06-14 setting. If Pr.06-14 is set to 03, the AC
drive will restart after the delay time set by Pr.06-15 is up.
06 - 16 User-Defined Low-Voltage Detection Level (Lv) Unit: 1
Settings 00 Disabled
440 ~ 600VDC Factory Setting: 00
06 - 17 User-Defined Low-Voltage Detection Time Unit: 0.1
Settings 0.1~ 3600.0 sec Factory Setting: 0.5