Chapter 5 Parameters|VFD-B-P Series
Revision April 2009, SW V1.00 5-77
This parameter also determines the waiting time before resuming operation after External
Baseblock and after Auto Restart after Fault (Pr.08-14).
When using a PG card with PG (encoder), speed search will begin at the actual PG (encoder)
feedback speed and accelerate to the setting frequency.
08 - 07
Current Limit for Speed Search
Unit: 1
V/f Control Settings 30 to 150%
Factory Setting: 110
Vector Control Settings 30 to 200%
Factory Setting: 150
This parameter is used to set the max. output current of the AC motor drive for speed search.
When executing speed search, the V/f curve will use the group 1 settings as the basic value.
The control method is set by parameter 00-09.
Output
Frequency
Output
Vol tage
08-06
08-05
08-04=01
08-06
08-05
08-04=02
Power
Input
Maximum Allowable
Power Loss Time
Baseblock Time
Speed Search
Speed
Synchronization
Detection
Maximum
Allowable Power
Baseblock Time
08 - 08 Skip Frequency 1 Upper Limit Unit: 0.01
08 - 09 Skip Frequency 1 Lower Limit Unit: 0.01
08 - 10 Skip Frequency 2 Upper Limit Unit: 0.01
08 - 11 Skip Frequency 2 Lower Limit Unit: 0.01
08 - 12 Skip Frequency 3 Upper Limit Unit: 0.01
08 - 13 Skip Frequency 3 Lower Limit Unit: 0.01
Settings 0.00 to 400.00Hz Factory Setting: 0.00
These parameters set the Skip Frequencies. It will cause the AC motor drive to never remain
within these frequency ranges with continuous frequency output.
These six parameters should be set as follows Pr.08-08 Pr.08-09 Pr.08-10 Pr.08-11
Pr.08-12 Pr.08-13.