Chapter 7 Troubleshooting |VFD-B-P Series
7-4 Revision April 2009, SW V1.00
7.5 Over Heat (OH)
AC motor drive overheats
Check if temperature of heat sink
3-20HP: greater than 100
O
-60HP: greater than 90
O
C
25 C
Yes
No
Temperature detection malfunctions.
Please contact DELTA.
No
No
Yes
Yes
Yes
No
Reduce load
If cooling fan functions normally
Change cooling fan
Check if surrounding temperature
is within specification
Adjust surrounding temperature
to specification
Maybe AC motor drive has malfunction or
misoperation due to noise. Please contact
DELTA.
Is load too large
Using Delta optional heatsink?
No
Yes
Check if the applying area and thickness
of thermal grease between the AC drive
and heatsink is within specification. Refer
to chapter 2 for details.
7.6 Overload
OL1/ OL2
OL
Reduce load or increase the power of AC motor drive
Check for correct settings at
Pr. 06-06 and 06-07
Ye s
Yes
No
No
Modify setting
Is load too large
Maybe AC motor drive has malfunction
or misoperation due to noise.

Other manuals for Delta VFD-B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-B Series and is the answer not in the manual?

Delta VFD-B Series Specifications

General IconGeneral
SeriesVFD-B
Cooling MethodFan cooling
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control ModeV/F control, Sensorless Vector Control
CommunicationRS-485
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity90% RH (non-condensing)
Altitude1000m (Derating required above 1000m)

Related product manuals