WARNING!
1. DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor
drive is easily damaged by high-pressure.
2. There are highly sensitive MOS components on the printed circuit boards. These components
are especially sensitive to static electricity. To prevent damage to these components, do not
touch these components or the circuit boards with metal objects or your bare hands.
3. Only qualified persons are allowed to install, wire and maintain AC motor drives.
CAUTION!
1. Some parameter settings will cause the motor to run immediately after applying power.
2. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,
high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic
particles.
3. Only use AC motor drives within specification. Failure to comply may result in fire, explosion or
electric shock.
4. To prevent personal injury, please keep children and unqualified people away from the
equipment.
5. When the motor cable between the AC motor drive and motor is too long, the layer insulation of
the motor may be damaged. Please use a frequency inverter duty motor or add an AC output
reactor to prevent damage to the motor. Refer to appendix B Reactor for details.
6. The rated voltage for the AC motor drive must be 240V ( 480V for 460V models, 600V for
575V models) and the mains supply current capacity must be 5000A RMS (10000A RMS for
the 40hp (30kW) models).

Other manuals for Delta VFD-B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-B Series and is the answer not in the manual?

Delta VFD-B Series Specifications

General IconGeneral
SeriesVFD-B
Cooling MethodFan cooling
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control ModeV/F control, Sensorless Vector Control
CommunicationRS-485
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity90% RH (non-condensing)
Altitude1000m (Derating required above 1000m)