Chapter 5 Parameters|VFD-B-P Series
Revision April 2009, SW V1.00 5-17
Parameter Explanation Settings
Factory
Setting
Custome
r
01: 1.5 power curve
02: 1.7 power curve
03: Square curve
04: Cube curve
11-01
Start-Up Frequency
of the Auxiliary
Motor
0.00 to 400.00 Hz 0.00
11-02
Stop Frequency of
the Auxiliary Motor
0.00 to 400.00 Hz 0.00
11-03
Time Delay before
Starting the Auxiliary
Motor
0.0 to 3600.0 sec 0.0
11-04
Time Delay before
Stopping the
Auxiliary Motor
0.0 to 3600.0 sec 0.0
11-05
Sleep/Wake Up
Detection Time
0.0 ~6550.0 sec 0.0
11-06 Sleep Frequency 0.00~Fmax 0.00
11-07 Wakeup Frequency 0.00~Fmax 0.00

Other manuals for Delta VFD-B Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-B Series and is the answer not in the manual?

Delta VFD-B Series Specifications

General IconGeneral
SeriesVFD-B
Cooling MethodFan cooling
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Control ModeV/F control, Sensorless Vector Control
CommunicationRS-485
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity90% RH (non-condensing)
Altitude1000m (Derating required above 1000m)