Chapter 4 Parameters|VFD-EL-W
116
Momentary Power Loss Action
1: Operation continues after momentary power loss, speed search starts
with the last frequency
2: Operation continues after momentary power loss, speed search starts
with the minimum frequency
Determines the operation mode when the drive restarts from a momentary power loss.
Maximum Allowable Power Loss Time
Determines the maximum time of allowable power loss. If the duration of a power loss exceeds
this parameter setting, the AC motor drive stops output after the power recovers.
The selected operation after power loss in Pr.08.04 is only executed when the maximum
allowable power loss time is ≤ 5 seconds and the AC motor drive keypad displays “Lv”. If the AC
motor drive is powered off due to overload, even if the maximum allowable power loss time is ≤
5 seconds, the drive does not execute the operation mode you set for Pr.08.04. In that case it
starts up normally.
1: Speed search starts with the last speed before B.B.
2: Speed search starts with the minimum speed (Pr.01.05)
Determines the AC motor drive restart method after an External Base Block is enabled.
Output frequency
(H)
Output voltage(V)
08.08 Current Limit
for Speed SearchSpeed
FWD Run
Time
B.B.
Fig 1:B.B. Speed Search with Last Output Frequency Downward Timing Chart
(Speed Search Current Attains Speed Search Level)
A
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
Speed Search
Synchronization speed detection