Diagram A
Please wind each wire four times around the core. The
reactor must be put as close to the inverter output as
possible.
NOTE:
600V Insulated Unshielded Cable
1. The table above gives approximate wire size for
zero phase reactors, but the selection is ultimately
governed by the type and diameter of the cable;
that is, the cable must fit through the center hole
of zero phase reactors.
2. When wiring, do not pass the grounding cable
through the zero phase reactor; only pass the
motor wire or power cable through the zero phase
reactor.
3. With longer motor cables the zero-phase reactor
can effectively reduce interference at the motor
output.