Chapter 2 Installation and WiringVFD-EL-W
24
2-3-2 Main Circuit Terminals
Frame A1
Frame A2
Frame B
Frame
Model
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
Maximum
Wire
Gauge
Minimum
Wire
Gauge
Screw Size
Tightening
Torque (±10%)
A1
VFD007EL21W(-1)
4 mm
2
(12 AWG)
4 mm
2
(12AWG)
M4 screw
15 kgf-cm
(13 in-lbf)
(1.47 Nm)
VFD007EL43W(-1)
2.5 mm
2
(14AWG)
A2
VFD015EL43W(-1)
B
VFD015EL21W(-1)
10 mm
2
(8 AWG)
10 mm
2
(8 AWG)
M4 screw
13 kgf-cm
(11.4 in-lbf)
(1.3 Nm)
VFD022EL21W(-1)
VFD022EL43W(-1)
2.5 mm
2
(14 AWG)
VFD040EL43W(-1)
VFD055EL43W(-1)
NOTE:
1. For installation at an ambient temperature of 50°C, select copper wires with temperature resistance of
75°C or 90°C. For installation at an ambient temperature over 50°C, select copper wires with temperature
resistance of 90°C or above.
2. For VFD007EL21W(-1) model: when install at Ta 40°C environment, use copper wires that are temperature
resistance to 75°C or 90°C; when install at Ta 40°C above environment, use copper wires that are
temperature resistance to 90°C or above.
3. When installing VFDxxxEL21W(-1), use wires that have a voltage rating of 300 V
AC
or above. When
installing VFDxxxEL43W(-1), use wires that have a voltage rating of 600 V
AC
or above.