Chapter 4 ParametersVFD-EL-W
47
Pr.
Parameter Name
Setting Range
Default
03.08
Fan Cooling Control
0: Fan is always ON
1: Fan is OFF after the AC motor drive stops for one
minute.
2: Fan is ON when the AC motor drive runs; fan is
OFF when the AC motor drive stops
3: Fan turns ON when temperature (IGBT) reaches
(60°C ON, 40°C OFF)
4: Fan is ON when the AC motor drive runs; fan is
OFF when the AC motor drive stops. Fan is in
stand-by mode at zero speed.
0
(For fan
cooling
models
only)
03.09
Reserved
03.10
Reserved
03.11
Mechanical Brake Release
Frequency
0.0020.00 Hz
0.00
03.12
Mechanical Brake Active
Frequency
0.0020.00 Hz
0.00
03.13
Display the Status of Multi-
function Output Terminal
Refer to Description of Parameter Settings
Read
only
03.14
Reserved