Chapter 4 ParametersVFD-EL-W
56
09 Communication Parameters
You can set this parameter during operation.
Pr.
Parameter Name
Setting Range
Default
09.00
Communication Address
1–254
1
09.01
Communication
Transmission Speed
0: Baud rate 4800 bps
1: Baud rate 9600 bps
2: Baud rate 19200 bps
3: Baud rate 38400 bps
1
09.02
Communication Fault
Treatment
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No treatment and no fault
3
09.03
Communication Time-Out
Detection
0.0: No function
0.1120.0 sec.
0.0
09.04
Communication Protocol
0: 7, N, 2 for ASCII
1: 7, E, 1 for ASCII
2: 7, O, 1 for ASCII
3: 8, N, 2 for RTU
4: 8, E, 1 for RTU
5: 8, O, 1 for RTU
6: 8, N, 1 for RTU
7: 8, E, 2 for RTU
8: 8, O, 2 for RTU
9: 7, N, 1 for ASCII
10: 7, E, 2 for ASCII
11: 7, O, 2 for ASCII
0
09.05
Reserved
09.06
Reserved
09.07
Communication Response
Delay Time
0–200 (unit: 2ms)
1
09.08
Communication Keypad
Selection
0: PU06
1: PU08
0