Chapter 5 Parameters_VFD-B Series 
Revision 10/2005, BE13, SW V4.08    5-43 
 
02- 06 
Line Start Lockout 
      Factory Setting: 00
  Settings  00  Disable. Operation status is not changed even if operation command source 
Pr.02-01 and/or Pr.02-14 is changed. 
    01  Enable. Operation status is not changed even if operation command source 
Pr.02-01 and/or Pr.02-14 is changed. 
    02  Disable. Operation status will change if operation command source Pr.02-01 
and/or Pr.02-14 is changed. 
    03  Enable. Operation status will change if operation command source Pr.02-01 
and/or Pr.02-14 is changed. 
This parameter determines the response of the drive when power on and operation command source is 
changed. 
Pr.02-06  Start lockout (Run when power is ON) 
Operation status when operation 
command source is changed 
0  Disable (AC motor drive will run)  Keep previous status 
1  Enable (AC motor drive won’t run)  Keep previous status 
2  Disable (AC motor drive will run) 
Change according to the new 
operation command source 
3  Enable (AC motor drive won’t run) 
Change according to the new 
operation command source 
When the operation command source is from external terminal and operation command is ON (FWD/REV-
DCM=close), the AC motor drive will operate according to Pr.02-06 after power is applied. <For terminals 
FWD and REV only> 
1.  When Pr.02-06 is set to 0 or 2, AC motor drive will run immediately. 
2.  When Pr.02-06 is set to 1 or 3, AC motor drive will remain stopped until operation command is received 
after previous operation command is cancelled.