Chapter 5 Parameters_VFD-B Series 
5-8   
Revision 10/2005, BE13, SW V4.08 
Parameter  Explanation  Settings 
Factory 
Setting
Customer
28: User-defined low-voltage detection    
29: Brake control (Desired frequency 
attained 3) 
   
03-04  Desired Frequency Attained 1  0.00 to 400.00 Hz  0.00   
00: Analog frequency meter 
01: Analog current meter 
02: Output voltage 
03: Output frequency command 
04: Output motor speed 
03-05  Analog Output Signal 
05: Load power factor (cos90
o
 to Cos0
o
) 
00 
 
a03-06 
Analog Output Gain  01 to 200%  100   
a03-07 
Digital Output Multiplying Factor  01 to 20  01   
a03-08 
Terminal Count Value   00 to 65500  00   
a03-09 
Preliminary Count Value 
00 to 65500  00 
 
03-10  Desired Frequency Attained 2  0.00 to 400.00 Hz  0.00   
00: Preliminary count value attained, no EF 
display 
03-11 
EF Active When Preliminary 
Count Value Attained 
01: Preliminary count value attained, EF 
active 
00 
 
00: Fan always ON 
01: 1 minute after AC motor drive stops, fan 
will be OFF 
02: AC motor drive runs and fan ON, AC 
motor drive stops and fan OFF 
03-12  Fan Control 
03: Fan ON to run when preliminary 
heatsink temperature attained 
00 
 
03-13  Brake Release Frequency  0.00 to 400.00Hz  0.00   
03-14  Brake Engage Frequency  0.00 to 400.00Hz  0.00   
 
Group 4 Input Function Parameters 
Parameter  Explanation  Settings 
Factory 
Setting
Customer
a04-00  AVI Analog Input Bias  0.00~200.00 %  0.00   
00: Positive bias   
04-01  AVI Bias Polarity 
01: Negative bias 
00 
 
a04-02  AVI Input Gain  1 to 200 %   100   
00: No AVI negative bias command   04-03  AVI Negative Bias,  
Reverse Motion Enable/Disable 
01: Negative bias: REV motion enabled 
00