Chapter 5 Parameters_VFD-B Series 
5-18   
Revision 10/2005, BE13, SW V4.08 
Parameter  Explanation  Settings 
Factory 
Setting
Customer
11-03 
Time Delay before Starting the 
Auxiliary Motor 
0.0 to 3600.0 sec  0.0 
 
11-04 
Time Delay before Stopping the 
Auxiliary Motor 
0.0 to 3600.0 sec  0.0 
 
11-05  Sleep/Wake Up Detection Time  0.0 ~6550.0 sec  0.0 
 
11-06  Sleep Frequency  0.00~Fmax  0.00 
 
11-07  Wakeup Frequency  0.00~Fmax  0.00 
 
 
5.2 Parameter Settings for Applications 
Speed Search 
Applications  Purpose  Functions 
Related 
Parameters
Windmill, winding machine, fan 
and all inertia load 
Restart free-running 
motor 
Before the free-running motor is 
completely stopped, it can be restarted 
without detecting motor speed. The AC 
motor drive will auto search motor speed 
and will accelerate when its speed is the 
same as the motor speed. 
08-06 
08-07 
08-19 
08-20 
DC Braking before Running 
Applications  Purpose  Functions 
Related 
Parameters
When e.g. windmills, fans and 
pumps rotate freely by wind or 
flow without applying power 
Keep the free-running 
motor at standstill. 
If the running direction of the free-running 
motor is not steady, please execute DC 
braking before start-up. 
08-00 
08-01