Chapter 5 Parameters_VFD-B Series 
5-58   
Revision 10/2005, BE13, SW V4.08 
04 - 19 
AVI Analog Input Delay  Unit: 0.01
  Settings  0.00 to 10.00 sec  Factory Setting: 0.05
04 - 20 
ACI Analog Input Delay  Unit: 0.01
  Settings  0.00 to 10.00 sec  Factory Setting: 0.05
04 - 21 
AUI Analog Input Delay  Unit: 0.01
  Settings  0.00 to 10.00 sec  Factory Setting: 0.05
These input delays can be used to filter noisy analog signals. 
 
04 - 22 
Analog Input Frequency Resolution 
      Factory Setting: 01
  Settings  00  0.01Hz 
    01  0.1Hz 
It is used to set the unit of the resolution of frequency command when the input source is analog signal. 
 
04 - 04 
Multi-function Input Terminal (MI1)  
 
  Factory Setting: 01
04 - 05 
Multi-function Input Terminal (MI2)  
 
  Factory Setting: 02
04 - 06 
Multi-function Input Terminal (MI3)  
 
  Factory Setting: 03
04 - 07 
Multi-function Input Terminal (MI4)  
 
  Factory Setting: 04
04 - 08 
Multi-function Input Terminal (MI5)  
 
  Factory Setting: 05
04 - 09 
Multi-function Input Terminal (MI6)  
 
  Factory Setting: 06