Chapter 5 Parameters_VFD-B Series 
Revision 10/2005, BE13, SW V4.08    5-47 
Group 3: Output Function Parameters 
03 - 00 
Multi-function Output Relay (RA1, RB1, RC1) 
 
  Factory Setting: 08
03 – 01 
Multi-function Output Terminal MO1  
 
  Factory Setting: 01
03 - 02 
Multi-function Output Terminal MO2 
 
  Factory Setting: 02
03 - 03 
Multi-function Output Terminal MO3 
 
  Factory Setting: 20
 
Settings  Function  Description 
00  No Function   
01  AC Drive Operational 
Active when there is an output from the drive or RUN command is 
“ON”. 
02  Master Frequency Attained 
Active when the AC motor drive reaches the output frequency 
setting. 
03  Zero Speed 
Active when Command Frequency is lower than the Minimum 
Output Frequency. 
04  Over-Torque Detection 
Active as long as over-torque is detected. (Refer to Pr.06-03 ~ 
Pr.06-05) 
05  Baseblock (B.B.) Indication 
Active when the output of the AC motor drive is shut off during 
baseblock. Base block can be forced by Multi-function input (setting 
9 or 10). 
06  Low-Voltage Indication  Active when low voltage(Lv) is detected. 
07  Operation Mode Indication  Active when operation command is controlled by external terminal. 
08  Fault Indication 
Active when faults occur (oc, ov, oH, oL, oL1, EF, cF3, HPF, ocA, 
ocd, ocn, GFF). 
09  Desired Frequency Attained 1 Active when the desired frequency (Pr.03-04) is attained. 
10   PLC Program Running  Active when PLC Program is running. 
11  PLC Program Step Completed Active for 0.5 sec each time the multi-step speed is attained.