Appendix B  Accessories_VFD-B Series 
B-38     Revision 10/2005, BE13 
B.9 Non-fuse Circuit Breaker Chart 
Per UL 508C, paragraph 45.8.4, part a: 
1.  For 1-phase drives, the current rating of the breaker shall be 4 times maximum input current rating. 
2.  For 3-phase drives, the current rating of the breaker shall be 4 times maximum output current rating. 
(Refer to Appendix A for rated input/output current) 
 
1-phase  3-phase 
Model 
Recommended 
non-fuse 
breaker (A) 
Model 
Recommended 
non-fuse 
breaker (A) 
Model 
Recommended 
non-fuse 
breaker (A) 
VFD007B21A  20  VFD007B23A  10  VFD220B23A  175 
VFD015B21A/B  30  VFD007B43A  5  VFD220B43A  100 
VFD022B21A  50  VFD007B53A  5  VFD220B53A  75 
    VFD015B23A/B 15  VFD300B23A  225 
    VFD015B43A  10  VFD300B43A  125 
    VFD015B53A  5  VFD300B53A  75 
    VFD022B23A  30  VFD370B23A  250 
    VFD022B43B  15  VFD370B43A  150 
    VFD022B53A  10  VFD370B53A  100 
    VFD037B23A  40  VFD450B43A  175 
    VFD037B43A  20  VFD450B53A  125 
    VFD037B53A  20  VFD550B43A/C  250 
    VFD055B23A  50  VFD550B53A  175 
    VFD055B43A  30  VFD750B43A/C  300 
    VFD055B53A  20  VFD750B53A  200 
    VFD075B23A  60     
    VFD075B43A  40     
    VFD075B53A  30     
    VFD110B23A  100     
    VFD110B43A  50     
    VFD110B53A  40     
    VFD150B23A  125     
    VFD150B43A  60     
    VFD150B53A  40     
    VFD185B23A  150     
    VFD185B43A  75     
    VFD185B53A  50