Chapter 5 Parameters_VFD-B Series 
5-114   
Revision 10/2005, BE13, SW V4.08 
11 - 05 
Sleep/Wake Up Detection Time 
Unit: 0.1
  Settings  0.0 to 6550.0 sec  Factory Setting: 0.0
11 - 06 
Sleep Frequency 
Unit: 0.01
  Settings  0.00 to Fmax Hz  Factory Setting: 0.00
11 - 07 
Wakeup Frequency 
Unit: 0.01
  Settings  0.00 to Fmax Hz  Factory Setting: 0.00
When the actual output frequency 
 Pr.11-06 and the time exceeds the setting of Pr.11-05, the AC motor 
drive will be in sleep mode. 
When  the  actual  frequency  command  >  Pr.11-07  and  the  time  exceeds  the  setting  of  Pr.11-05,  the  AC 
motor drive will restart. 
When the AC motor drive is in sleep mode, frequency command is still calculated by PID. When frequency 
reaches wake up frequency, AC motor drive will accelerate from Pr.01-05 min. frequency by V/f curve. 
The wake up frequency must be higher than sleep frequency. 
11-07
11-06
01-08
01-05
11-05
Frequency
The limit of 
decel. time
frequency calculated by PID
output
frequency
Time
The limit of 
accel. time
 
Fmin
 
 
Fsleep
 
Fcmd=0
Fout = 0
 
lower bound 
of frequency
Fmin<Fsleep<
lower bound 
of frequency