Chapter 5 Parameters_VFD-B Series 
Revision 10/2005, BE13, SW V4.08    5-37 
Group 2: Operation Method Parameters 
02 – 00 
aSource of First Master Frequency Command 
      Factory Setting: 00
  Settings  00  Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs UP/DOWN. 
Last used frequency saved. 
    01  AVI  0 ~ +10VDC 
    02  ACI  4 ~ 20mA 
    03  AUI  -10 ~ +10VDC 
    04  RS-485 serial communication (RJ-11). Last used frequency saved. 
    05  RS-485 serial communication (RJ-11). Last used frequency not saved. 
    06  Combined use of master and auxiliary frequency command 
See Pr. 02-10 to 02-12 
02 – 13 
aSource of Second Master Frequency Command 
      Factory Setting: 00
  Settings  00  Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN. Last used 
frequency saved. 
    01  AVI  0 ~ +10VDC 
    02  ACI  4 ~ 20mA 
    03  AUI  -10 ~ +10VDC 
    04  RS-485 serial communication (RJ-11). Last used frequency saved. 
    05  RS-485 serial communication (RJ-11). Last used frequency not saved. 
    06  Combined use of master and auxiliary frequency command 
See Pr. 02-10 to 02-12 
These parameters set the Master Frequency Command Source of the AC motor drive.