Chapter 5 Parameters_VFD-B Series 
Revision 10/2005, BE13, SW V4.08    5-73 
06 - 01 
Over-Current Stall Prevention during Acceleration  Unit: 1
  Settings  20 to 250%   Factory Setting: 170
A setting of 100% is equal to the Rated Output Current of the drive. 
During acceleration, the AC drive output current may increase abruptly and exceed the value specified by 
Pr.06-01 due to rapid acceleration or excessive load on the motor. When this function is enabled, the AC 
drive will stop accelerating and keep the output frequency constant until the current drops below the 
maximum value. 
06-01
Over-Current
Detection
Level
Output 
Frequency
Over-Current Stall
prevention during
Acceleration,
frequency held
output current
time
setting
frequency
previous acceleration time
actual acceleration time when over-current stall 
prevention is enabled
 
06 - 02 
Over-current Stall Prevention during Operation  Unit: 1
  Settings  20 to 250%   Factory Setting: 170
If the output current exceeds the setting specified in Pr.06-02 when the drive is operating, the drive will 
decrease its output frequency to prevent the motor stall. If the output current is lower than the setting 
specified in Pr.06-02, the drive will accelerate again to catch up with the set frequency command value.