Chapter 5 Parameters_VFD-B Series 
5-100   
Revision 10/2005, BE13, SW V4.08 
      if(reg_crc & 0x01){  /* LSB(b0)=1 */ 
        reg_crc=(reg_crc>>1) ^ 0xA001; 
      }else{ 
        reg_crc=reg_crc >>1; 
      } 
    } 
  } 
 return reg_crc; 
} 
 
3.5  Address list
 
The contents of available addresses are shown as below: 
Content  Address  Function 
AC drive 
Parameters 
GGnnH 
GG means parameter group, nn means parameter number, for example, the 
address of Pr 4-01 is 0401H. Referencing to chapter 5 for the function of 
each parameter. When reading parameter by command code 03H, only one 
parameter can be read at one time. 
Bit 0-1 
00B: No function 
01B: Stop  
10B: Run  
11B: Jog + Run 
Command 
Write only 
2000H 
Bit 2-3  Reserved 
   
Bit 4-5 
00B: No function 
01B: FWD 
10B: REV 
11B: Change direction 
Bit 6-7 
00B: Comm. forced 1st accel/decel  
01B: Comm. forced 2nd accel/decel  
10B: Comm. forced 3rd accel/decel 
11B: Comm. forced 4th accel/decel 
Bit 8-11  Represented 16 step speeds. 
Bit 12 
0: No comm. multi step speed or accel/decel time 
1: Comm. multi step speed or accel/decel time 
Command 
Write only 
2000H 
Bit 13-15  Reserved 
2001H  Frequency command  
Bit 0  1: EF (external fault) on   
Bit 1  1: Reset 
Command 
Write only 
2002H 
Bit 2-15  Reserved 
Error code: 
00: No error occurred 
  2100H 
01: Over-current (oc)