Chapter 5 Parameters_VFD-B Series 
Revision 10/2005, BE13, SW V4.08    5-9 
Parameter  Explanation  Settings 
Factory 
Setting
Customer
    02: Negative bias: REV motion disabled     
00: No function  01   
01: Multi-Step speed command 1   
 
04-04 
Multi-Function Input Terminal 1 
(MI1)  
02: Multi-Step speed command 2   
 
03: Multi-Step speed command 3     
04: Multi-Step speed command 4  02   
05: External reset (N.O.)     
06: Accel/Decel inhibit     
07: Accel/Decel time selection command 1     
04-05 
Multi-Function Input Terminal 2 
(MI2) 
08: Accel/Decel time selection command 2     
09: External base block (N.O.)  03 
 
10: External base block (N.C.)     
04-06 
Multi-Function Input Terminal 3 
(MI3) 
11: Up: Increment master frequency     
12: Down: Decrement master frequency  04   
13: Counter reset     
14: Run PLC program     
04-07 
Multi-Function Input Terminal 4 
(MI4) 
15: Pause PLC program     
16: Auxiliary motor No.1 output disable  05   
17: Auxiliary motor No.2 output disable     
18: Auxiliary motor No.3 output disable     
04-08 
Multi-Function Input Terminal 5 
(MI5) 
19: Emergency stop (N.O.)     
20: Emergency stop (N.C.)  06   
21: Master frequency selection AVI/ACI     
22: Master frequency selection AVI/AUI     
23: Operation command selection 
(keypad/external terminals) 
   
24: Auto accel/decel mode disable   
25: Forced stop (N.C.)   
26: Forced stop (N.O.) 
 
 
27: Parameter lock enable (N.O.)   
 
28: PID function disabled   
 
29: Jog FWD/REV command   
 
30: External reset (N.C.)   
 
31: Source of second frequency command 
enabled 
 
 
32: Source of second operation command 
enabled 
 
 
04-09 
Multi-Function Input Terminal 6 
(MI6)
 
33: One shot PLC